PAGE 43 of 68 VX2200 TECHNICAL MANUAL VER1.5
INSTALLATION DIRECTIONS
Installation and maintenance must be carried out by specialized engineers only. Do not install the
components of the system in humid environments or near heat sources. Make sure that the power supplies
present in the system are not connected to the mains during the installation of devices. Before powering the
system, check that the cabling is correct. The wiring diagrams must always be followed (in case of different
applications contact Videx technical) and always use cables as outlined below. It is advisable to separate the
Mains lines (lift, electricity, electricity lock, etc.) from the BUS lines (A distance of at least 10 cm) to avoid
electrostatic discharge and magnetic influence that could cause problems to the on the system. It is also very
important to set all dip switches before powering up. If any are changed for any reason it is necessary to
power that device down and then back up for the change to take effect.
GUIDELINES TO OVERCOME EXTREME ELECTROMAGNETIC INTERFERENCE
In situations of EMI where interference is affecting the functions of the system it is advised to add the
following:
Loop the mains cable twice through the ferrite core (Model No. RT310-190-160 or
equivalent).
Loop the bus cable which connects the video distributor to the videophone
twice through the ferrite core (Model No. RKCF-13-A5 or equivalent)
For the mains cable:-
FERRITE MATERIAL: K5B
PART NUMBER A B C
IMPEDANCE
(
Ω
)
STANDARD
PACK
25MHz 100MHz
19.0031.00 40RT-310-190-160-K5B 16.00 68 115
'A'
'C'
'B'
For the videophone:-
Ferrite Material: A
Part No
'A' Dim
'B' Dim
'C' Dim
'D' Dim
Impedan
Applicable
Cable Max
Dia
Standard
Pack
Pieces
Fig
25 MHz
100 Mhz
RKCF-13-A5
31.50
1.00 14.00 1.00 31.50 1.00 32.50 1.00 150 250 13 32 1
DIM 'C'
DIM 'D'
DIM 'B'
DIM 'A'
FIG 1